Georgia Legionella Compliance & Water Quality Standards
Executive Overview
Georgia Department of Public Health enforces water management standards under Ga. Comp. R. & Regs. 290-5-6 and CMS guidelines.
Governing Public Health Agency & Reporting Mandates
- Agency Name: Georgia Department of Public Health (DPH)
- Infectious Disease Reporting Hotline: (866) 782-4584 (1-866-PUB-HLTH 24/7 Epi)
- Main Contact Phone: (404) 657-2700
- Official Portal: https://dph.georgia.gov
- Mandatory Reporting Window: All diagnosed cases of Legionellosis (Legionnaires' disease / Pontiac fever) must be reported to Georgia Department of Public Health (DPH) within 24 hours.
Statutory & Regulatory Citations
- Ga. Comp. R. & Regs. 290-5-6: Rules and Regulations for Hospitals in Georgia (Georgia Department of Public Health) — Enforced via State Licensing Inspection
Regional Water Chemistry & Disinfection Profile
- Dominant Municipal Disinfectant:
FREE CHLORINE - Typical Distribution Residual: 0.5 – 2 mg/L (ppm)
- Average Water Hardness: 2 GPG (34 mg/L CaCO₃) — Classified as SOFT
- Calculated Scaling Risk: LOW
- pH Operating Range: 6.9 – 7.5
- Regional Water Contaminants / Vectors: Piedmont surface water organics, Pipe corrosion in soft water
Mandatory Environmental Testing Cadence
| System Type | Facility Scope | Frequency | Required Test Method | Compliance Notes |
|---|---|---|---|---|
| Domestic Hot | healthcare | Quarterly_90d | CDC ELITE Culture ISO11731 | Quarterly testing in hospitals and long-term care centers. |
Action Thresholds & CAPA Containment Protocols
Potable Water — Level 3 Critical Emergency (10+ CFU/mL)
- Mandatory Containment Protocol:
- Report to GA DPH within 24 hours, perform remediation.
- Clearance Verification Retest: Within 7 days.
- Mandatory Public Health Notification: Within 24 hours.
Surveyor & CMS Audit Defense Checklist
- Active ASHRAE 188 Water Management Plan (WMP) updated within the last 12 months.
- Water Safety Team Charter with designated Infection Prevention, Facilities, and Clinical leads.
- Process Flow Diagrams (PFDs) identifying point-of-entry, booster pumps, calorifiers, and distal sample locations.
- Daily / Weekly Physical & Chemical Monitoring Logs (temperature and disinfectant residual).
- Closed-Loop Corrective Action Logs (CAPA) documenting immediate remediation for any out-of-spec reading.