State Jurisdictionfree chlorine8 GPG (moderate scale risk)

Montana Legionella Compliance & Water Quality Standards

Authoritative statutory citations, mandatory testing schedules, chemical thresholds, and 1-click ASHRAE 188 Water Management Plan generation for Montana facilities.

Pre-configured Montana WMP Generator
Pre-filled with Minimum Standards for All Healthcare Facilities in Montana mandates, free chlorine residuals, and local alert thresholds.
Dominant Disinfectant
free chlorine
Target residual: 0.5–2.0 mg/L in distribution
Water Hardness
8 GPG (137 mg/L)
Scaling Risk: moderate
Reporting Window
24 Hours
Mandatory notification upon positive culture
Reporting Hotline
(406) 444-0273 (Communicable Disease Epidemiology)
Montana Dept of Public Health & Human Services (DPHHS)

Statutory Citations & Enactments

Primary public health codes governing Legionella prevention in Montana.

ARM 37.106.301
Minimum Standards for All Healthcare Facilities in Montana
Agency: Montana DPHHSState Licensing Inspection

Mandatory Environmental Testing Cadence

System TypeFacility ScopeCadenceStandard MethodRequirement Details
Domestic HothealthcareQuarterly 90dCDC ELITE Culture ISO11731Quarterly testing in licensed healthcare facilities.

Action Thresholds & Corrective Action (CAPA) Protocols

Mandatory remedial containment protocols when bacterial concentrations exceed baseline control limits.

Potable Water — Level 3 Critical Emergency10+ CFU/mL
  • Notify Montana DPHHS within 24 hours.
Retest window: 7 daysReport in 24h

Montana Legionella Compliance & Water Quality Standards

Executive Overview

Montana DPHHS enforces healthcare water safety standards under ARM 37.106.301.

Governing Public Health Agency & Reporting Mandates

  • Agency Name: Montana Dept of Public Health & Human Services (DPHHS)
  • Infectious Disease Reporting Hotline: (406) 444-0273 (Communicable Disease Epidemiology)
  • Main Contact Phone: (406) 444-5622
  • Official Portal: https://dphhs.mt.gov
  • Mandatory Reporting Window: All diagnosed cases of Legionellosis (Legionnaires' disease / Pontiac fever) must be reported to Montana Dept of Public Health & Human Services (DPHHS) within 24 hours.

Statutory & Regulatory Citations

  • ARM 37.106.301: Minimum Standards for All Healthcare Facilities in Montana (Montana DPHHS) — Enforced via State Licensing Inspection

Regional Water Chemistry & Disinfection Profile

  • Dominant Municipal Disinfectant: FREE CHLORINE
  • Typical Distribution Residual: 0.5 – 1.9 mg/L (ppm)
  • Average Water Hardness: 8 GPG (137 mg/L CaCO₃) — Classified as MODERATE
  • Calculated Scaling Risk: MODERATE
  • pH Operating Range: 7.2 – 7.9
  • Regional Water Contaminants / Vectors: Mountain runoff turbidity, Hard well water

Mandatory Environmental Testing Cadence

System TypeFacility ScopeFrequencyRequired Test MethodCompliance Notes
Domestic HothealthcareQuarterly_90dCDC ELITE Culture ISO11731Quarterly testing in licensed healthcare facilities.

Action Thresholds & CAPA Containment Protocols

Potable Water — Level 3 Critical Emergency (10+ CFU/mL)

  • Mandatory Containment Protocol:
    • Notify Montana DPHHS within 24 hours.
  • Clearance Verification Retest: Within 7 days.
  • Mandatory Public Health Notification: Within 24 hours.

Surveyor & CMS Audit Defense Checklist

  1. Active ASHRAE 188 Water Management Plan (WMP) updated within the last 12 months.
  2. Water Safety Team Charter with designated Infection Prevention, Facilities, and Clinical leads.
  3. Process Flow Diagrams (PFDs) identifying point-of-entry, booster pumps, calorifiers, and distal sample locations.
  4. Daily / Weekly Physical & Chemical Monitoring Logs (temperature and disinfectant residual).
  5. Closed-Loop Corrective Action Logs (CAPA) documenting immediate remediation for any out-of-spec reading.

Frequently Asked Questions: Montana Water Safety & Legionella

How is Legionellosis reported in Montana?

Reports must be submitted within 24 hours to Montana DPHHS Epidemiology.

Ready to build a compliant Water Management Plan for Montana?

Instantly generate your customized ASHRAE 188 / CMS QSO-17-30 compliant plan pre-populated with local statutory citations, water chemistry, and action limits.